12 17.5 24kV Pemutus Sirkuit Vakum Dalam Ruangan, Seri GPVN-E
Kondisi Lingkungan
Suhu sekitar: -25 ℃ ~ + 45 ℃, rata-rata saben dina: ≤35 ℃
Dhuwur: 1000m (Standar);bisa nganti 4500m kanggo pesenan khusus;
Kelembapan relatif: rata-rata saben dina ≤95%, rata-rata saben wulan ≤90%;
Intensitas lindhu ≤8 derajat;
Acara sing ditrapake kudu bebas saka inflammables, bahan peledak, korosif lan geter abot.
Model
GPVN -12Kv/17.5kV Pemutus Sirkuit Vakum Tegangan Tinggi AC Indoor
Spesifikasi Teknis
Ora. | Item | Unit | data | ||||||
1 | voltase dirating | kV | 7.2~12(15/17.5) | ||||||
2 | Frekuensi dirating | Hz | 50/60 | ||||||
3 | Rated saiki | A | 630.1000.1250 | 1600 | 2000,2500,3150 | 4000 | |||
4 | Rated short-circuit breaking saiki | kA | 20 | 25 | 31.5 | 31.5 | 40 | 40 | 50 |
5 | Rated short-circuit nggawe saiki | kA | 50 | 63 | 80 | 80 | 100 | 100 | 125 |
6 | Dirating short-time tahan saiki | kA | 20 | 25 | 31.5 | 31.5 | 40 | 40 | 50 |
7 | Rated puncak tahan saiki | kA | 50 | 63 | 80 | 80 | 100 | 100 | 125 |
8 | Rated pull-out breaking saiki | kA | 12.6 | 12.6 | 16 | 16 | 20 | ||
9 | Dirating metu-saka-phase earthing fault breaking saiki | kA | 17.4 | 21.7 | 27.4 | 27.4 | 34.7 | 34.7 | 43.5 |
10 | Dirating short-circuit breaking saiki breaking wektu | kaping | 50 | 30 | 30 | 12 | |||
11 | Urutan operasi sing dirating | O-0.3s-CO-180s-CO | O-180s-CO-180s-CO | ||||||
12 | Rated breaking saiki saka bank kapasitor tunggal | A | 630 | ||||||
13 | Rated breaking saiki saka back to back kapasitor bank | A | 400 | ||||||
14 | 1 min.Frekuensi daya tahan voltase | kV | Phase to phase/ to earth: 42, ing kontak mbukak:48 | ||||||
15 | Impuls kilat tahan voltase | kV | Phase to phase/ to earth: 75, ing kontak mbukak:85 | ||||||
16 | urip mekanik | kaping | 20000 | ||||||
17 | wektu nutup | ms | ≤75 | ||||||
18 | Wektu mbukak | ms | ≤60 | ||||||
19 | Wektu panyimpenan daya ing voltase dirating | s | ≤10 |
Ukuran Garis GPVN-12E
GPVN-24□ Pemutus Sirkuit Vakum Tegangan Tinggi Dalam Ruangan
Spesifikasi Teknis
Ora. | Item | Unit | data | |||
1 | voltase dirating | kV | 24 | |||
2 | Frekuensi dirating | Hz | 50/60 | |||
3 | Rated saiki | A | 630 1250 1600 2000 2500 3150 4000 | |||
4 | Rated short-circuit breaking saiki | kA | 20 | 25 | 31.5 | 31.5 |
5 | Rated short-circuit nggawe saiki | kA | 50 | 63 | 80 | 80 |
6 | Rated short-circuit tahan saiki (4s) | kA | 20 | 25 | 31.5 | 31.5 |
7 | Rated puncak tahan saiki | kA | 50 | 63 | 80 | 80 |
8 | Dirating metu-saka-langkah breaking saiki | kA |
|
| 12.6 | 12.6 |
9 | Rated breaking saiki saka out-of-phase earth fault | kA | 17.4 | 21.7 | 27.4 | 27.4 |
10 | Rated breaking kaping saka short-circuit breaking saiki | kaping | 50 | |||
11 | Rated urutan operasi |
| O-0.3s-CO-180s-CO | |||
12 | Rated breaking saiki saka bank kapasitor tunggal | A | 630 | |||
13 | Rated breaking saiki saka back-to-back kapasitor bank | A | 400 | |||
14 | 1 min.Frekuensi daya tahan voltase | kV | 50 | |||
15 | Impuls kilat tahan voltase | kV | 125 | |||
16 | urip mekanik | kaping | 20000 | |||
17 | wektu nutup | ms | 75 | |||
18 | Wektu mbukak | ms | 60 | |||
19 | Wektu panyimpenan ing voltase dirating | s | 10 |