GPN2S/GPN2E-40.5kV Cubicle jinis Gas Insulated Switchgear

Katrangan singkat:

Tipe Cubicle Gas Insulated Switchgear (CGIS) yaiku switchgear insulated gas ing njero ruangan, dipasang pabrik, ditutupi logam, kanggo aplikasi busbar tunggal, kalebu "Tipe Ijo" GPN2E-40.5, GPN2N-40.5 lan "Tipe Standar" GPN2S- 40.5.


Detail Produk

Tag produk

Ringkesan

Tipe Cubicle Gas Insulated Switchgear (CGIS) yaiku switchgear insulated gas ing njero ruangan, dipasang pabrik, ditutupi logam, kanggo aplikasi busbar tunggal, kalebu "Tipe Ijo" GPN2E-40.5, GPN2N-40.5 lan "Tipe Standar" GPN2S- 40.5.
"Tipe Ijo" GPN2N-40.5 diinovasi kanggo nggunakake nitrogen murni minangka gas insulasi kanggo produk seri kanthi teknologi insulasi gas Non-SF6, sing wis nggawa perlindungan lingkungan ijo asli saka switchgear terisolasi gas.
"Tipe ijo" GPN2E-40.5 nggabungake teknologi canggih campuran terisolasi gas (SF6+N2) lan pemutus vakum, ngidini peralatan bisa digunakake kanthi cara sing luwih dipercaya lan ramah lingkungan.
"Tipe standar" GPN2S-40.5 saka 100% SF6 terisolasi, kinerja dhuwur lan gampang digunakake.
Kanthi manufaktur digital modern lan tes otomatis ditambah karo sensor, monitor lan teknologi proteksi, CGIS cocog kanggo panjaluk distribusi daya.CGIS utamané cocog kanggo industri sing nduweni syarat linuwih kayata Power Networks, Mining, Rail Transportation, Petrokimia Plants, Wind Farms lan Metropolitan Rail Systems.
Kondisi operasi normal
Switchgear dhasar dirancang kanggo kahanan layanan normal kanggo switchgear njero ruangan GB 3906, DL / T404 lan IEC 62271-200.Nilai watesan ing ngisor iki, antara liya, ditrapake:
Suhu udara sekitar
Suhu udara maksimal: +45 ℃
Suhu udara minimal: -25 ℃
Suhu maksimum rata-rata saben dina: +35 ℃
Kelembapan:
Nilai rata-rata saben dina saka asor relatif: ≤ 95%
Nilai rata-rata saben wulan saka asor relatif: ≤ 90%
Nilai rata-rata saben dina tekanan uap banyu: ≤ 2,2 × 10-3MPa
Nilai rata-rata saben wulan tekanan uap banyu: ≤ 1,8 × 10-3MPa
Dhuwur: ≤ 1000m
Udhara lingkungan ora kena polusi kanthi bledug, asap,
gas korosif lan/utawa gampang kobong, uap utawa uyah.

Kahanan layanan khusus
Produk kasebut uga bisa ditrapake kanggo akeh kahanan layanan khusus.
Yen kahanan layanan ngluwihi kahanan layanan normal, sing metu saka standar GB 11022 lan IEC 62271-1, hubungi GP luwih dhisik kanggo konfirmasi:
Dhuwuré luwih dhuwur tinimbang 1000m.
Suhu lingkungan sing luwih dhuwur.
Suhu lingkungan sing luwih murah.
Liyane kahanan lingkungan khusus.

Ngurangi emisi gas omah kaca
CGIS nggabungake teknologi canggih Nitrogen murni utawa terisolasi gas campuran (SF6 + N2) lan pemutus vakum, pilihan dhasar sing digawe dening GP kanggo mbantu nyuda efek omah kaca.SF6 (sulphur-hexafluoride) ana ing daftar gas omah kaca ing Protokol Kyoto, kanthi Potensi Pemanasan Global (GWP) 23.000.Akeh sistem switchgear voltase medium liyane nggunakake gas SF6 minangka medium insulasi.Kebocoran gas SF6 saka switchgear nyebabake ancaman efek omah kaca lan owah-owahan iklim sing ana gandhengane.
Kanthi komitmen kita kanggo nglindhungi lingkungan, CGIS mbantu nyuda emisi gas omah kaca kanthi nggunakake teknologi terisolasi gas campuran bebarengan karo teknologi switch vakum.
Pengurangan 100% utawa 50% ing SF6 digayuh kanthi nggunakake pemutus terisolasi gas campuran Nitrogen (N2).Nitrogen minangka komponèn paling gedhé ing udara lan produk dekomposisi busur ora beracun.Digabungake karo konektor plug-in lan sifat modular saka panel njamin gampang instalasi lan extension tanpa mbutuhake aktivitas penanganan gas ekstra ing situs.

Kaluwihan

● 70% Pengurangan Ukuran Switchroom
Desain lapangan listrik sing dioptimalake digabungake karo kinerja insulasi sing apik, ngasilake produk switchgear kompak sing bisa digunakake kanthi aman lan andal.
Ngirit papan 70% dibandhingake karo switchgear terisolasi udara.
Retrofitting menyang switchroom ana gampang.
Ngurangi biaya lahan gardu.
● Safety Maksimal Kanggo Operator lan Peralatan
Tekanan fungsional minimal saka cubicle yaiku 0.00MPa (20 ℃).Tegese, sanajan ing kahanan sing abot, isih njaga tingkat insulasi sing dirating lan njaga kabeh fungsi sing dirating.Amarga tekanan gas sing sithik, sanajan gas metu saka switchgear, cubicle isih bisa terus diuripake.Interlock listrik lan mekanik sing dipercaya dirancang ing antarane pemutus sirkuit lan switch telung posisi kanggo nyegah misoperation.
● Instalasi Gampang / Operasi lan Biaya Pangopènan sing Murah
Panel ing tengah bisa gampang dibusak kanggo pangopènan tanpa obah panel tetanggan, nambah kasedhiyan.

Parameter teknis

Umum

Unit

Tipe standar

GPN2S-40.5

Tipe Ijo

GPN2E-40.5

Tipe Ijo

GPN2N-40.5

voltase dirating

kV

36/38/40.5

36/38/40.5

36/38/40.5

Dirating frekuensi daya tahan voltase (1 min)

Kanggo bumi / fase kanggo fase

kV

95

95

95

Ing jarak ngisolasi

kV

118

118

118

Kanggo bumi / fase kanggo fase

kV

185

185

185

Ing jarak ngisolasi

kV

215

215

215

Frekuensi dirating

Hz

50/60

50/60

50/60

Rated saiki

A

1250, 2500, 3150

1250, 2500

1250, 2500

Kapasitas pecah bank kapasitor tunggal

A

400/400

400/400

400/400

Rated kabel charging breaking current

A

50

50

50

Rated shortcircuit breaking saiki

kA

20/25/31.5

20/25/31.5

31.5

Rated short circuit nggawe saiki (puncak)

kA

50/63/80

50/63/80

80

Dirating wektu cendhak tahan saiki lan toleransi wektu

kA/s

20/3, 25/3, 31,5/3s

20/3, 25/3, 31,5/3s

31.5/3s

Rated puncak tahan saiki

kA

50/63/80

50/63/80

80

Urutan operasi

 

O-0.3s-CO-180s-CO

O-0.3s-CO-180s-CO

O-0.3s-CO-180s-CO

Sistem gas terisolasi gas

 

100% SF6

50% SF6+50%N2

100%N2

Tingkat kebocoran taunan

%/Y

≤ 0.1

≤ 0.1

≤ 0.1

Tekanan gas terukur (abs, 20˚C)

MPa

0.12

0.12

0.12

Tekanan alarm (abs, 20˚C)

MPa

0.11

0.11

0.11

Tekanan operasi minimum (abs, 20˚C)

MPa

0.10

0.10

0.10

Derajat Pangreksan

Tangki gas

 

IP65

IP65

IP65

Enclosure

 

IP4X

IP4X

IP4X

Motor lan trip coil

Pengisian motor pemutus sirkuit

W

90

90

90

Dirating daya kumparan nutup

W

220

220

220

Dirating daya mbukak kumparan

W

220

220

220

Rated voltase saka sirkuit tambahan

V

DC 24, 48, 110, 220;AC220

DC 24, 48, 110, 220;AC220

DC 24, 48, 110, 220;AC220

1 min frekuensi daya tahan voltase saka sirkuit tambahan

kV

2

2

2

Dimensi lan Bobot

Ukuran (W × D × H) 1250A

mm

600×1600×2400

600×1500×2400

800×1700×2300

Ukuran (W × D × H) 2500A

mm

800×1600×2400

800×1500×2400

900×1700×2300

Bobot 1250A

kg

800 ~ 1000

800 ~ 1000

800 ~ 1000

Bobot 2500A

kg

1100 ~ 1400

1100 ~ 1400

1100 ~ 1400

Struktur tipe standar GPN2S-40.5 lan tipe ijo GPN2E-40.5

img

Tipe standar GPN2S-40.5kV

img2

Jinis ijo GPN2E-40.5kV

1. Unit pangayoman lan kontrol
2. Kompartemen tegangan rendah
3. mekanisme VCB
4. Embedded Pole vakum sirkuit mbobol
5. Low voltase kompartemen lawang
6. Indikator Kapadhetan gas
7. Tangki gas VCB
8. 3-posisi mekanisme ngalih
9. 3-posisi ngalih
10. Busbar utama

11. Tangki bensin busbar utama
12. Tutup ngarep
13. Surge arrester
14. Piranti relief tekanan tangki gas busbar utama
15. Inner-conthong kabel busing
16. Terminal Kab
17. Kab
18. Tutup mburi
19. Piranti relief meksa saka tank gas VCB
20. CT

img3

IST 3-mekanisme posisi

img4

IST 3-posisi ngalih

img5

Tangki bensin GPN2S VCB

img6

GPN2S-40.5 VCB

Struktur tipe standar GPN2S-40.5 lan tipe ijo GPN2E-40.5Struktur tipe ijo GPN2N (No-SF6)

img7

Jinis ijo GPN2N-40.5kV

1. Unit pangayoman lan kontrol
2. Kompartemen tegangan rendah
3. mekanisme VCB
4. Embedded Pole vakum sirkuit mbobol
5. Low voltase kompartemen lawang
6. Indikator Kapadhetan gas
7. Tangki gas VCB
8. 3-posisi mekanisme ngalih
9. 3-posisi ngalih
10. Busbar utama
11. Tangki bensin busbar utama

12. Tutup ngarep
13. Surge arrester
14. Piranti relief tekanan tangki gas busbar utama
15. Inner-conthong kabel busing
16. Terminal Kab
17. Kab
18. Tutup mburi
19. Piranti relief meksa saka tank gas VCB
20. CT
21. Bar bumi
22. Trafo tegangan (opsional)

Pemutus sirkuit vakum dipasang, dene kutub sing dipasang telung fase disusun kanthi vertikal menyang tangki gas pemutus sirkuit.
Amarga teknologi ngoper vakum, busur diwatesi ing interrupter vakum, nyuda volume exhaust gas insulasi.Ngoper vakum nduweni kinerja dhuwur ing sirkuit cendhak sing kerep lan akeh aplikasi ngoper beban.

img8

Pemasangan PT

img9

CT ing kompartemen kabel

img10
img11
img12

Ukuran garis ukuran standar GPN2S-40.5kV

img13

Ukuran garis saka GPN2E-40.5kV jinis ijo

img14

  • Sadurunge: