GPN2S/GPN2E-40.5kV Cubicle jinis Gas Insulated Switchgear
Ringkesan
Tipe Cubicle Gas Insulated Switchgear (CGIS) yaiku switchgear insulated gas ing njero ruangan, dipasang pabrik, ditutupi logam, kanggo aplikasi busbar tunggal, kalebu "Tipe Ijo" GPN2E-40.5, GPN2N-40.5 lan "Tipe Standar" GPN2S- 40.5.
"Tipe Ijo" GPN2N-40.5 diinovasi kanggo nggunakake nitrogen murni minangka gas insulasi kanggo produk seri kanthi teknologi insulasi gas Non-SF6, sing wis nggawa perlindungan lingkungan ijo asli saka switchgear terisolasi gas.
"Tipe ijo" GPN2E-40.5 nggabungake teknologi canggih campuran terisolasi gas (SF6+N2) lan pemutus vakum, ngidini peralatan bisa digunakake kanthi cara sing luwih dipercaya lan ramah lingkungan.
"Tipe standar" GPN2S-40.5 saka 100% SF6 terisolasi, kinerja dhuwur lan gampang digunakake.
Kanthi manufaktur digital modern lan tes otomatis ditambah karo sensor, monitor lan teknologi proteksi, CGIS cocog kanggo panjaluk distribusi daya.CGIS utamané cocog kanggo industri sing nduweni syarat linuwih kayata Power Networks, Mining, Rail Transportation, Petrokimia Plants, Wind Farms lan Metropolitan Rail Systems.
Kondisi operasi normal
Switchgear dhasar dirancang kanggo kahanan layanan normal kanggo switchgear njero ruangan GB 3906, DL / T404 lan IEC 62271-200.Nilai watesan ing ngisor iki, antara liya, ditrapake:
Suhu udara sekitar
Suhu udara maksimal: +45 ℃
Suhu udara minimal: -25 ℃
Suhu maksimum rata-rata saben dina: +35 ℃
Kelembapan:
Nilai rata-rata saben dina saka asor relatif: ≤ 95%
Nilai rata-rata saben wulan saka asor relatif: ≤ 90%
Nilai rata-rata saben dina tekanan uap banyu: ≤ 2,2 × 10-3MPa
Nilai rata-rata saben wulan tekanan uap banyu: ≤ 1,8 × 10-3MPa
Dhuwur: ≤ 1000m
Udhara lingkungan ora kena polusi kanthi bledug, asap,
gas korosif lan/utawa gampang kobong, uap utawa uyah.
Kahanan layanan khusus
Produk kasebut uga bisa ditrapake kanggo akeh kahanan layanan khusus.
Yen kahanan layanan ngluwihi kahanan layanan normal, sing metu saka standar GB 11022 lan IEC 62271-1, hubungi GP luwih dhisik kanggo konfirmasi:
Dhuwuré luwih dhuwur tinimbang 1000m.
Suhu lingkungan sing luwih dhuwur.
Suhu lingkungan sing luwih murah.
Liyane kahanan lingkungan khusus.
Ngurangi emisi gas omah kaca
CGIS nggabungake teknologi canggih Nitrogen murni utawa terisolasi gas campuran (SF6 + N2) lan pemutus vakum, pilihan dhasar sing digawe dening GP kanggo mbantu nyuda efek omah kaca.SF6 (sulphur-hexafluoride) ana ing daftar gas omah kaca ing Protokol Kyoto, kanthi Potensi Pemanasan Global (GWP) 23.000.Akeh sistem switchgear voltase medium liyane nggunakake gas SF6 minangka medium insulasi.Kebocoran gas SF6 saka switchgear nyebabake ancaman efek omah kaca lan owah-owahan iklim sing ana gandhengane.
Kanthi komitmen kita kanggo nglindhungi lingkungan, CGIS mbantu nyuda emisi gas omah kaca kanthi nggunakake teknologi terisolasi gas campuran bebarengan karo teknologi switch vakum.
Pengurangan 100% utawa 50% ing SF6 digayuh kanthi nggunakake pemutus terisolasi gas campuran Nitrogen (N2).Nitrogen minangka komponèn paling gedhé ing udara lan produk dekomposisi busur ora beracun.Digabungake karo konektor plug-in lan sifat modular saka panel njamin gampang instalasi lan extension tanpa mbutuhake aktivitas penanganan gas ekstra ing situs.
Kaluwihan
● 70% Pengurangan Ukuran Switchroom
Desain lapangan listrik sing dioptimalake digabungake karo kinerja insulasi sing apik, ngasilake produk switchgear kompak sing bisa digunakake kanthi aman lan andal.
Ngirit papan 70% dibandhingake karo switchgear terisolasi udara.
Retrofitting menyang switchroom ana gampang.
Ngurangi biaya lahan gardu.
● Safety Maksimal Kanggo Operator lan Peralatan
Tekanan fungsional minimal saka cubicle yaiku 0.00MPa (20 ℃).Tegese, sanajan ing kahanan sing abot, isih njaga tingkat insulasi sing dirating lan njaga kabeh fungsi sing dirating.Amarga tekanan gas sing sithik, sanajan gas metu saka switchgear, cubicle isih bisa terus diuripake.Interlock listrik lan mekanik sing dipercaya dirancang ing antarane pemutus sirkuit lan switch telung posisi kanggo nyegah misoperation.
● Instalasi Gampang / Operasi lan Biaya Pangopènan sing Murah
Panel ing tengah bisa gampang dibusak kanggo pangopènan tanpa obah panel tetanggan, nambah kasedhiyan.
Parameter teknis
Umum | Unit | Tipe standar GPN2S-40.5 | Tipe Ijo GPN2E-40.5 | Tipe Ijo GPN2N-40.5 | |
voltase dirating | kV | 36/38/40.5 | 36/38/40.5 | 36/38/40.5 | |
Dirating frekuensi daya tahan voltase (1 min) | Kanggo bumi / fase kanggo fase | kV | 95 | 95 | 95 |
Ing jarak ngisolasi | kV | 118 | 118 | 118 | |
Kanggo bumi / fase kanggo fase | kV | 185 | 185 | 185 | |
Ing jarak ngisolasi | kV | 215 | 215 | 215 | |
Frekuensi dirating | Hz | 50/60 | 50/60 | 50/60 | |
Rated saiki | A | 1250, 2500, 3150 | 1250, 2500 | 1250, 2500 | |
Kapasitas pecah bank kapasitor tunggal | A | 400/400 | 400/400 | 400/400 | |
Rated kabel charging breaking current | A | 50 | 50 | 50 | |
Rated shortcircuit breaking saiki | kA | 20/25/31.5 | 20/25/31.5 | 31.5 | |
Rated short circuit nggawe saiki (puncak) | kA | 50/63/80 | 50/63/80 | 80 | |
Dirating wektu cendhak tahan saiki lan toleransi wektu | kA/s | 20/3, 25/3, 31,5/3s | 20/3, 25/3, 31,5/3s | 31.5/3s | |
Rated puncak tahan saiki | kA | 50/63/80 | 50/63/80 | 80 | |
Urutan operasi | O-0.3s-CO-180s-CO | O-0.3s-CO-180s-CO | O-0.3s-CO-180s-CO | ||
Sistem gas terisolasi gas | 100% SF6 | 50% SF6+50%N2 | 100%N2 | ||
Tingkat kebocoran taunan | %/Y | ≤ 0.1 | ≤ 0.1 | ≤ 0.1 | |
Tekanan gas terukur (abs, 20˚C) | MPa | 0.12 | 0.12 | 0.12 | |
Tekanan alarm (abs, 20˚C) | MPa | 0.11 | 0.11 | 0.11 | |
Tekanan operasi minimum (abs, 20˚C) | MPa | 0.10 | 0.10 | 0.10 | |
Derajat Pangreksan Tangki gas | IP65 | IP65 | IP65 | ||
Enclosure | IP4X | IP4X | IP4X | ||
Motor lan trip coil Pengisian motor pemutus sirkuit | W | 90 | 90 | 90 | |
Dirating daya kumparan nutup | W | 220 | 220 | 220 | |
Dirating daya mbukak kumparan | W | 220 | 220 | 220 | |
Rated voltase saka sirkuit tambahan | V | DC 24, 48, 110, 220;AC220 | DC 24, 48, 110, 220;AC220 | DC 24, 48, 110, 220;AC220 | |
1 min frekuensi daya tahan voltase saka sirkuit tambahan | kV | 2 | 2 | 2 | |
Dimensi lan Bobot Ukuran (W × D × H) 1250A | mm | 600×1600×2400 | 600×1500×2400 | 800×1700×2300 | |
Ukuran (W × D × H) 2500A | mm | 800×1600×2400 | 800×1500×2400 | 900×1700×2300 | |
Bobot 1250A | kg | 800 ~ 1000 | 800 ~ 1000 | 800 ~ 1000 | |
Bobot 2500A | kg | 1100 ~ 1400 | 1100 ~ 1400 | 1100 ~ 1400 |
Struktur tipe standar GPN2S-40.5 lan tipe ijo GPN2E-40.5
Tipe standar GPN2S-40.5kV
Jinis ijo GPN2E-40.5kV
1. Unit pangayoman lan kontrol
2. Kompartemen tegangan rendah
3. mekanisme VCB
4. Embedded Pole vakum sirkuit mbobol
5. Low voltase kompartemen lawang
6. Indikator Kapadhetan gas
7. Tangki gas VCB
8. 3-posisi mekanisme ngalih
9. 3-posisi ngalih
10. Busbar utama
11. Tangki bensin busbar utama
12. Tutup ngarep
13. Surge arrester
14. Piranti relief tekanan tangki gas busbar utama
15. Inner-conthong kabel busing
16. Terminal Kab
17. Kab
18. Tutup mburi
19. Piranti relief meksa saka tank gas VCB
20. CT
IST 3-mekanisme posisi
IST 3-posisi ngalih
Tangki bensin GPN2S VCB
GPN2S-40.5 VCB
Struktur tipe standar GPN2S-40.5 lan tipe ijo GPN2E-40.5Struktur tipe ijo GPN2N (No-SF6)
Jinis ijo GPN2N-40.5kV
1. Unit pangayoman lan kontrol
2. Kompartemen tegangan rendah
3. mekanisme VCB
4. Embedded Pole vakum sirkuit mbobol
5. Low voltase kompartemen lawang
6. Indikator Kapadhetan gas
7. Tangki gas VCB
8. 3-posisi mekanisme ngalih
9. 3-posisi ngalih
10. Busbar utama
11. Tangki bensin busbar utama
12. Tutup ngarep
13. Surge arrester
14. Piranti relief tekanan tangki gas busbar utama
15. Inner-conthong kabel busing
16. Terminal Kab
17. Kab
18. Tutup mburi
19. Piranti relief meksa saka tank gas VCB
20. CT
21. Bar bumi
22. Trafo tegangan (opsional)
Pemutus sirkuit vakum dipasang, dene kutub sing dipasang telung fase disusun kanthi vertikal menyang tangki gas pemutus sirkuit.
Amarga teknologi ngoper vakum, busur diwatesi ing interrupter vakum, nyuda volume exhaust gas insulasi.Ngoper vakum nduweni kinerja dhuwur ing sirkuit cendhak sing kerep lan akeh aplikasi ngoper beban.