12/24/40.5kV Rana Majelis Lan Interlocking
Rana Majelis 5GP.320.010 Diagram Instalasi
(800mm jembaré switchgear tengah diselehake)
Rana Majelis 5GP.320.010 Dhaftar Arrangement
Ora. | jeneng | Nggambar no. | Qty.(pc/set) |
1 | Bracket penyangga tengen | 8GP.123.011 | 1 |
2 | Plat sambungan tengen | 5GP.235.011 | 1 |
3 | Tag sing nuduhake | 8GP.866.014 | 1 |
4 | Sambungan kiwa | 5GP.235.010 | 1 |
5 | Bracket ndhukung kiwa | 8GP.123.010 | 1 |
6 | Sambungan welding | 5GP.174.016.1(Kanggo VD4) | 2 |
5GP.174.016.2(Kanggo GPVN) | |||
5GP.174.016.3(Kanggo VB2) | |||
7 | Down shutter gate | 8GP.320.010 | 1 |
8 | Blok macet 8 | DK-8 | 8 |
9 | Plat braket | 8GP.123.013 | 3 |
Ora. | jeneng | Nggambar no. | Qty.(pc/set) |
10 | Sambungan welding | 5GP.174.017.1(Kanggo VD4, 40kA) | 2 |
5GP.174.017.2(Kanggo VD4, 31.5kA) | |||
5GP.174.017.3(Kanggo GPVN) | |||
5GP.174.017.4(Kanggo VB2) | |||
11 | Tag sing nuduhake | 8GP.866.012 | 1 |
12 | Tag sing nuduhake | 8GP.866.013 | 2 |
13 | Plat braket | 8GP.123.012 | 3 |
14 | Rana ndhuwur | 8GP.320.011 | 1 |
15 | Pandhuan rod | 8GP.234.011(Kanggo VD4, GPVN) | 2 |
8GP.234.011.1(Kanggo VB2) | |||
16 | Lengan stopper | 8GP.210.011 | 2 |
Dhaptar pangaturan rana spesifikasi liyane
Kode | 5GP.320.010.1 | 5GP.320.010.2 | 5GP.320.010.3 | 5GP.320.010.4 | 5GP.320.010.5 |
Jembaré kabinèt | 650 mm | 700 mm | 840 mm | 900 mm | 1000 mm |
Gapura ndhuwur | 8GP.320.011.1 | 8GP.320.011.2 | 8GP.320.011.3 | 8GP.320.011.4 | 8GP.320.011.5 |
Gapura mudhun | 8GP.320.010.1 | 8GP.320.010.2 | 8GP.320.010.3 | 8GP.320.010.4 | 8GP.320.010.5 |
Majelis Rana 5GP.320.011
(1000mm jembaré switchgear tengah diselehake)
Piranti Mekanisme Rana 5GP.320.011 Dhaftar Arrangement
(1000mm jembaré switchgear tengah diselehake)
Ora. | jeneng | Nggambar no. | Qty.(pc/set) |
1 | Bracket penyangga tengen | 8GP.123.276 | 1 |
2 | Plat sambungan tengen | 5GP.235.012 | 1 |
3 | Tag sing nuduhake | 8GP.866.014 | 1 |
4 | Plat sambungan kiwa | 5GP.235.013 | 1 |
5 | Bracket ndhukung kiwa | 8GP.123.275 | 1 |
6 | Majelis las sambungan | 5GP.174.281 | 2 |
7 | Mudhun rana | 8GP.320.273 | 1 |
8 | Blok macet 10 | DK-10 | 8 |
Ora. | jeneng | Nggambar no. | Qty.(pc/set) |
9 | Plat braket | 8GP.123.278 | 3 |
10 | Sambungan sambungan las | 5GP.174.282 | 2 |
11 | Tag sing nuduhake | 8GP.866.012 | 1 |
12 | Tag sing nuduhake | 8GP.866.013 | 2 |
13 | Plat braket | 8GP.123.277 | 3 |
14 | Rana ndhuwur | 8GP.320.274 | 1 |
15 | Pandhuan rod | 8GP.234.272 | 2 |
16 | Lengan stopper | 8GP.210.011 | 2 |
Dhaptar pangaturan rana spesifikasi liyane
Kode | 5GP.320.011.1 | 5GP.320.011/JY | 5GP.320.011.2 | 5GP.320.011.3 |
Jembaré kabinèt | 800 mm | 1000 mm (Isolasi) | 1100 mm | 1200 mm |
Gapura ndhuwur | 8GP.320.274.1 | 5GP.320.275 | 8GP.320.274.2 | 8GP.320.274.3 |
Gapura mudhun | 8GP.320.273.1 | 5GP.320.275.1 | 8GP.320.273.2 | 8GP.320.273.3 |
Wigati: 5GP.320.275 kanggo insulating rana dening piring SMC ing tengah lan loro mburi dening piring baja, Déwan rana liyane yen perlu insulating gapura mangga nemtokake.
Mekanisme operasi switch earthing piranti interlock (Kanggo operasi drive arm sambungan) 5GP.363.010.1 diagram perakitan
Instruksi Piranti Interlock
Piranti interlock ditambahake interlock mbalikke karo lawang mburi kang dirancang ing basis saka asli 5GP.363.010 grounding ngalih mekanisme operasi piranti interlock.Yaiku, sawise switch earthing ditutup lan mbukak lawang mburi (sealing plate), interlock asli isih bisa ngoperasikake switch earthing, nanging interlock iki ora bisa.Sampeyan kudu nutup lawang mburi (plat sealing) dhisik supaya bisa ngoperasikake switch earthing.
Prinsip kerja piranti interlock diganti lengan ngunci No.Nalika lawang mburi (sealing plate) mbukak, lengen kunci mlebu menyang bolongan kothak kabinet (ukuran 35X35 dianjurake), earthing switch ora bisa dilakokno.
Mekanisme operasi switch earthing piranti interlock (Kanggo operasi drive arm sambungan)
5GP.363.010.1 dhaftar noto.
Ora. | jeneng | Nggambar no. | Qty.(pc/set) |
1 | bantalan | 8GP.263.011 | 1 |
2 | Sektor | 8GP.192.010 | 1 |
3 | Sektor | 8GP.192.011 | 1 |
4 | Lengan sumbu | 8GP.210.014.1 | 2 |
5 | Sektor | 8GP.151.041 | 1 |
6 | Lengan sumbu | 8GP.211.061 | 1 |
7 | Sektor | 8GP.151.039 | 1 |
8 | Lengan sumbu | 8GP.211.062 | 1 |
9 | Bolt M5×12 | GB70-85 | 1 |
10 | Sektor | 8GP.151.042 | 1 |
11 | Sektor | 8GP.151.043 | 1 |
12 | rod operasi | 8GP.200.013.1 (Long 1432 kanggo ambane kabinet 1500 ambane) | 1 |
8GP.200.013.2 (Long 1590 kanggo ambane kabinet 1660) | 1 | ||
13 | Papan sing ndhukung | 8GP.161.058 | 1 |
8GP.161.058.1(Kanggo opsi) | 1 |
Ora. | jeneng | Nggambar no. | Qty.(pc/set) |
14 | Panutup | 8GP.017.011.1 | 1 |
15 | krenjang | 5GP.043.022 | 1 |
16 | Papan sing ndhukung | 8GP.161.059 | 1 |
17 | Panggeser | 8GP.143.010 | 2 |
18 | Lengan sumbu | 8GP.211.058 | 1 |
19 | Lengan stopper | 8GP.211.057 | 3 |
20 | Dhukungan dhasar | 8GP.043.019 | 1 |
21 | Nutup nuduhake | 8GP.866.010 | 1 |
22 | Majelis rod sambungan | 5GP.233.030.1 | 1 |
5GP.233.030.3(Kanggo opsi) | 1 | ||
23 | Bukak nuduhake | 8GP.866.011 | 1 |
24 | Ngunci lengen | 8GP.211.201 | 1 |
25 | Plat sumbat untu | 8GP.151.044 | 1 |
26 | Lengan sumbu | 8GP.211.060 | 2 |
27 | Tag | 8GP.860.010 | 1 |
28 | Spring tekanan | 8GP.282.201 | 1 |
29 | Penguncian Lengan Pengikat Bolt | 8GP.920.002 | 1 |
Cathetan:
1. No. 1~12 deleng kaca sadurunge.
2. No.. 22 Sambungan rod Déwan, lengen sambungan wis loro ukuran: Kabinet tengah kadohan 60mm ing umum.Yen perlu jarak tengah 80mm, priksa kaca 17 instruksi perakitan lengen sambungan, lan tulisake nalika pesen.
Mekanisme operasi switch earthing piranti interlock (Kanggo operasi drive gear bevel) 5GP.577.1001
Mekanisme operasi switch earthing piranti interlock (Kanggo operasi bevel gear drive) 5GP.577.1001 dhaptar susunan
Ora. | jeneng | Nggambar no. | Qty.(pc/set) |
1 | bantalan | 8GP.263.011 | 1 |
2 | Plat stopper | 8GP.151.084 | 2 |
3 | Lengan sumbu | 8GP.210.014.1 | 2 |
4 | Sektor | 8GP.151.041 | 1 |
5 | Lengan sumbu | 8GP.210.014.2 | 1 |
6 | Bolt M 5X12 Kab | GB70-85 | 1 |
7 | Sektor | 8GP.151.042 | 1 |
8 | Sektor | 8GP.151.043 | 1 |
9 | Lengan sumbu | 8GP.210.014.3 | 1 |
Ora. | jeneng | Nggambar no. | Qty.(pc/set) |
10 | Lengan stopper | 8GP.210.322 | 1 |
11 | rod operasi | 8GP.174.214 | 1 |
12 | Panutup | 8GP.017.011.2 | 1 |
13 | Dhukungan dhasar | 5GP.043.022 | 1 |
14 | Panggeser | 8GP.143.010 | 2 |
15 | Papan sing ndhukung | 8GP.161.059 | 1 |
16 | Papan sing ndhukung | 8GP.161.058 | 1 |
17 | Plat sumbat untu | 8GP.151.044 | 1 |
18 | Tag | 8GP.860.010 | 1 |
Cathetan: 1. Iki mekanisme kudu interlocked karo lawang mudhun, mangga nemtokake nalika nindakake.