GPR-24(12)kV Series Ring Unit Utama Switchgear
Ringkesan
GPR-24 seri Ring Unit Utama minangka extensible, SF6 terisolasi switchgear, karo voltase dirating 12 & 24 kV.Kabeh bagean urip HV ana ing tank gas kedap udara, sing digawe saka stainless steel 3mm.Kabèh Déwan ngoper wis SF6 terisolasi, lan bebas saka pengaruh external, mesthekake linuwih gedhe saka layanan lan pangopènan free.Kanthi ekstensi busbar tipe plug-in, Unit Utama Ring seri GPR-24 bisa dadi kombinasi gratis lan modularisasi lengkap.Ekstensi busbar wis lulus tes jinis kanggo daya lan stabilitas termal, lan kanthi terisolasi lan dilindhungi, nuduhake linuwih lan safety.Unit Utama Ring seri GPR-24 cocok kanggo kabeh jaringan MV nganti 24 kV, kabeh stasiun listrik kompak, gardu distribusi daya ing kabeh industri penting, kayata industri bensin-kimia, industri metalurgi lan pertambangan, lan kabeh gardu trafo lan tenaga angin. sistem.
Fitur
1. Teknik proses majeng kanggo tank gas
Sistem nglereni lan punching laser sing dikontrol digital lan sistem welding laser telung dimensi lan limang sumbu sing diimpor saka Jerman kanthi njamin kekencangan lan keseragaman kabeh tangki gas.
Sistem deteksi bocor helium kanthi otomatis lan integral, digawe dening SEILER Vakuumtechnik GmbH, liwat ndeteksi bocor Helium kanthi spektrograf massa, ndadekke tingkat bocor gas saben taun nganti kurang saka 0,02%, njamin umur tangki bensin luwih saka 30 taun.
Teknik proses lanjutan kanggo bagean.
Kabeh bagean terisolasi resin epoksi, kalebu kutub terisolasi, diprodhuksi dening sistem pencampuran vakum / tekanan gelatinisasi resin epoksi kanthi otomatis lan digital saka Hedrich (Jerman).
Konektor busbar, konektor kabel, plug mburi lan bagean terisolasi karet silikon liyane diprodhuksi dening sistem pencampuran / tekanan gelatinisasi silikon kanthi otomatis lan digital saka VOGEL (Swiss).
2. Solusi sing apik kanggo produk
Kanthi struktur cilik lan kompak, unit fungsional dhasar K, T, V, B lan C duwe ukuran seragam: 350 * 800 * 1380 mm (jembar * ambane * dhuwur) .
Solusi lengkap:
Versi tunggal: unit saklar pemutus beban, unit sekering saklar, unit pemutus sirkuit vakum, unit subseksi busbar, unit kabel, unit metering, lsp.
Versi blok bisa digawe saka loro, telu, papat, lima utawa enem unit fungsional.
Unit tunggal lan versi blok bisa disambungake kanthi konektor busbar kanthi fleksibel.
3. Daya adaptasi sing kuat kanggo lingkungan
Sistem konduktif utami wis kebak disegel ing tank gas SF6 lan ora bakal dipengaruhi dening lingkungan njaba, gumantung saka impact saka embun, bledug, kabut uyah, etc. Mulane, GPR-24 seri bisa Applied ing macem-macem kahanan layanan abot. .
Data Teknis 12kV
Katrangan | Unit | Unit LBS | Unit switch-sekring | Unit VCB | Unit sub-bagian busbar | |
voltase dirating | kV | 12 | 12 | 12 | 12 | |
Frekuensi daya tahan tegangan (1 menit) | Phase to phase/bumi | kV | 42 | 42 | 42 | 42 |
Nyebrang jarak isolasi | kV | 48 | 48 | 48 | 48 | |
Impuls tahan voltase | Phase to phase/bumi | kV | 75, (95)* | 75, (95)* | 75, (95)* | 75, (95)* |
Nyebrang jarak isolasi | kV | 85, (110)* | 85, (110)* | 85, (110)* | 85, (110)* | |
Frekuensi dirating | Hz | 50,60 | 50,60 | 50,60 | 50,60 | |
Rated saiki | A | 630 | ① | 630 | 630 | |
Rated short circuit breaking saiki | kA |
| ② | 20,(25)* |
| |
Dirating wektu cendhak tahan saiki | kA/s | 20/3, (20/4, 25/1)* |
| 20/3, (20/4, 25/3)* | 20/3, (20/4, 25/1)* | |
Rated puncak tahan saiki | kA | 50, (63)* |
| 50, (63)* | 50, (63)* | |
Rated short circuit nggawe saiki | kA | 50, (63)* | ② | 50, (63)* | 50, (63)* | |
Rated transfer saiki | A |
| 1800 |
|
| |
Rated beban aktif breaking saiki | A | 630 |
|
| 630 | |
Rated loop tertutup saiki breaking | A | 630 |
|
| 630 | |
5% dirating beban aktif breaking saiki | A | 31.5 |
|
| 31.5 | |
Rated urutan operasi |
|
|
| O-0.3s-CO-180s-CO |
| |
Umur mekanik | Ops. | 5000 | 5000 | 10000 | 5000 | |
Umur listrik |
| E3 |
| E2 | E3 | |
Ketebalan stainless steel | mm | 3.0 | ||||
Rated SF6tekanan | kPa | 30 (ing 20 ℃, 101.3kPa) | ||||
Tingkat kebocoran taunan | <0,02% | |||||
Tes perawatan banyu | 12kV 24 jam (ing 30 kPa ing banyu) | |||||
Tes busur internal | 20kA 1s | |||||
Gelar pangayoman | Tangki gas | IP 67 | ||||
nduwèni sekring | IP 67 | |||||
GPR kandang |
| IP 4X |
Data Teknis 24kV
Katrangan | Unit | Unit LBS | Unit switch-sekring | Unit VCB | Unit sub-bagian busbar | |
voltase dirating | kV | 24 | 24 | 24 | 24 | |
Frekuensi daya tahan tegangan (1 menit) | Phase to phase/bumi | kV | 50, (65)* | 50, (65)* | 50, (65)* | 50, (65)* |
Nyebrang jarak isolasi | kV | 64, (79)* | 64, (79)* | 64, (79)* | 64, (79)* | |
Impuls tahan voltase | Phase to phase/bumi | kV | 95, (125)* | 95, (125)* | 95, (125)* | 95, (125)* |
Nyebrang jarak isolasi | kV | 110, (145)* | 110, (145)* | 110, (145)* | 110, (145)* | |
Frekuensi dirating | Hz | 50, 60 | 50, 60 | 50, 60 | 50, 60 | |
Rated saiki | A | 630 | ① | 630 | 630 | |
Rated short circuit breaking saiki | kA |
| ② | 20 |
| |
Dirating wektu cendhak tahan saiki | kA/s | 20/3, (20/4)* |
| 20/3, (20/4)* | 20/3, (20/4)* | |
Rated puncak tahan saiki | kA | 50 |
| 50 | 50 | |
Rated short circuit nggawe saiki | kA | 50 | ② | 50 | 50 | |
Rated transfer saiki | A |
| 1400 |
|
| |
Rated beban aktif breaking saiki | A | 630 |
|
| 630 | |
Rated loop tertutup saiki breaking | A | 630 |
|
| 630 | |
5% dirating beban aktif breaking saiki | A | 31.5 |
|
| 31.5 | |
Rated urutan operasi |
|
|
| O-0.3s-CO-180s-CO |
| |
Umur mekanik | Ops. | 5000 | 5000 | 10000 | 5000 | |
Umur listrik |
| E3 |
| E2 | E3 | |
Ketebalan stainless steel | mm | 3.0 | ||||
Rated tekanan SF6 | kPa | 30 (ing 20 ℃, 101.3kPa) | ||||
Tingkat kebocoran taunan | <0,02% | |||||
Tes perawatan banyu | 24kV 24 jam (ing 30 kPa ing banyu) | |||||
Tes busur internal | 20kA 1s | |||||
Gelar pangayoman | Tangki gas | IP 67 | ||||
nduwèni sekring | IP 67 | |||||
GPR kandang | IP 4X |
Cathetan:
① Rated saiki saka switch-sekring unit gumantung ing rating saka sekring: ≤100A
② Rated short circuit breaking/nggawe saiki saka switch-sekring unit gumantung ing rating saka sekring
* Nilai ing kurung kanggo syarat khusus, hubungi produsen utawa supplier kanggo informasi luwih lengkap
Ringkesan Seri GPR24
1. Tipe tank tunggal
Cathetan:
1. Nilai ing kurung sing ditandhani "*" yaiku produk ing 24kV, frekuensi daya tahan voltase 65/79kV;
2. Yen ana akeh banget komponen secondary ing konfigurasi, kompartemen tambahan kanggo wong-wong mau bisa diinstal ing ndhuwur panel, dhuwuré 400mm.
2. GPR24 Blok tipe-1 kanggo 12kV & 24kV (frekuensi daya tahan tegangan: 50/64kV)
Cathetan:
Yen ana akeh banget komponen sekunder ing konfigurasi, kompartemen tambahan kanggo wong-wong mau bisa dipasang ing ndhuwur GPR, dhuwuré 400mm.